Bench:Ratio

Duct size and CFM calculator

Size a round or rectangular duct from airflow and velocity.

Set by your design standard and noise limits.

Optional. Enter one side to get the other.

Duct area
530.874 cm² (82.2856 in²)
Round duct diameter
259.986 mm (10.2357 in)

Formula

A = Q / v, D = √(4A / π), width = A / height, D_e = 1.30 (a × b)^0.625 / (a + b)^0.25

Q is airflow in m³/s, v is velocity in m/s and A is the duct's cross-section area. D_e is the equivalent round diameter that gives the same friction loss for the same airflow as a rectangular duct a × b, both in inches.

Diagram

Duct sizingRound duct (side view)Airflow QDRectangular (cross-section)a (width)bArea A = Q / v Round: D = √(4A / π)Friction-equivalent: D_e = 1.30 (a × b)^0.625 / (a + b)^0.25
For a given airflow Q and velocity v, the duct area is Q / v. A rectangular duct needs the same area, or the same friction-equivalent diameter.

How it is calculated

  1. Convert airflow to m³/s and velocity to m/s.
  2. Duct area = airflow / velocity.
  3. Round duct diameter: D = √(4A / π).
  4. Rectangular duct: width = area / height. The friction-equivalent diameter is D_e = 1.30 (a × b)^0.625 / (a + b)^0.25.

Higher velocity means a smaller duct but more noise and pressure loss.

Worked examples

  1. A branch duct

    400 CFM at 700 ft/min. Result: Duct area: 530.874 cm² (82.2856 in²); Round duct diameter: 259.986 mm (10.2357 in).

  2. A larger duct

    1,000 CFM at 900 ft/min. Result: Duct area: 1,032.26 cm² (160 in²); Round duct diameter: 362.534 mm (14.273 in).

  3. A rectangular duct

    400 CFM at 700 ft/min with an 8 in height. Result: Rectangular width needed: 261.257 mm (10.2857 in); Friction-equivalent round diameter: 251.378 mm (9.89676 in).

Key terms

CFM
Cubic feet per minute, the usual US unit for airflow.
Design velocity
The air speed you aim for in the duct. It affects noise and friction.
Duct area
The cross-section through which air moves.
Equivalent diameter
The round duct size that behaves like a rectangular duct. Area-equivalent and friction-equivalent sizes differ.
Friction rate
Pressure lost per length of duct. Professional design methods balance it with velocity.
Aspect ratio
The ratio of a rectangular duct's long side to its short side. Very flat ducts perform worse.

Assumptions and limits

Uses the velocity method. Professional duct design also checks friction rate, total pressure, fittings and noise (for example with ACCA Manual D for homes). Available duct sizes and codes vary, so confirm with a qualified designer. See the disclaimer.

Learn more

Related calculators