How to Size a Duct from Airflow: The Velocity Method
Last reviewed 2026-10-12
A duct has to carry a given airflow without making too much noise or wasting fan energy. The velocity method is a quick first estimate.
The core idea
Duct area = airflow / velocity. For 400 CFM at 700 ft/min the area is 0.571 ft², which is about 82 in². A round duct with that area is about 10.2 in across.
Why velocity matters
Faster air needs a smaller duct but makes more noise and loses more pressure. Slower air is quieter but needs a bigger, costlier duct. The right velocity depends on the application and your design standard.
Rectangular ducts
A rectangular duct with the same area does not have the same friction as a round one. The friction-equivalent diameter shows which round duct behaves like your rectangle. Very flat rectangles perform worse.
What professionals add
Real duct design also checks friction rate, fittings, total pressure and fan capacity, for example using ACCA Manual D for homes. Treat this tool as a starting estimate.