Bench:Ratio

Voltage drop calculator

Find the voltage drop and power loss in a cable run.

Line-to-line for three-phase.

75 °C is a common design assumption. Use your code's value.

Optional. Compare against your own design target.

Resistance of one conductor
0.190099 Ω (6.33662 Ω/km)
Voltage drop
7.60394 V
Voltage drop (% of source)
3.30606%
Voltage at the load
222.396 V
Power lost in the cable
152.079 W
Against your target
Exceeds 3%. Try a larger conductor or a shorter run.

Formula

ΔV = I × R × 2 (single-phase or DC) or I × R × √3 (three-phase), R = ρ × L / A

ρ is the conductor's resistivity at its temperature, L is the one-way length and A is the cross-section area. Resistivity is 1.724 × 10⁻⁸ Ω·m for copper and 2.82 × 10⁻⁸ Ω·m for aluminium at 20 °C, corrected by 0.393% (copper) or 0.403% (aluminium) per °C.

Diagram

Voltage dropVSourceR cableLoadIΔV = I × RV load = V − ΔVΔV = I × R × 2 (single-phase or DC) ΔV = I × R × √3 (three-phase)R = ρ × L / A % drop = ΔV / V × 100
The cable has resistance, so some voltage is lost along it. Current flows out and back in a two-wire circuit, so the length counts twice.

How it is calculated

  1. Choose the circuit type and enter the voltage, current and one-way length.
  2. Pick the conductor material and size, and the conductor temperature.
  3. Resistivity at that temperature: ρ = ρ₂₀ × (1 + α × (T − 20)). Resistance R = ρ × L / A.
  4. Voltage drop = I × R × 2 for single-phase or DC, or I × R × √3 for balanced three-phase.
  5. Percent drop = ΔV / V × 100. Power lost = I² × R × 2 (or × 3).

Voltage drop targets such as 3% for a branch and 5% overall are widely quoted design guidelines, but the rules that apply to you come from your own code.

Worked examples

  1. A long single-phase run

    20 A at 230 V over 30 m of 12 AWG copper at 75 °C: R = 0.19 Ω per conductor, so ΔV = 20 × 0.19 × 2 = 7.6 V, which is 3.3% and exceeds a 3% target.

  2. Upsize the wire

    The same run in 8 AWG: R = 0.075 Ω, so ΔV = 3.0 V, or 1.3%. The cable now loses 60 W instead of 152 W.

  3. Three-phase

    32 A at 400 V over 50 m of 10 mm² copper at 20 °C: R = 0.0862 Ω, so ΔV = √3 × 32 × 0.0862 = 4.78 V, which is 1.19%.

Key terms

Voltage drop
The voltage lost along a cable because of its resistance.
Resistivity (ρ)
A material property. Copper is 1.724 × 10⁻⁸ Ω·m and aluminium 2.82 × 10⁻⁸ Ω·m at 20 °C.
One-way length
The distance from the source to the load. A two-wire circuit carries current both ways.
Conductor temperature
Resistance rises as a conductor heats up, by about 0.39% per °C for copper.
Reactance
An AC effect from the cable's magnetic field. It adds to the drop in large conductors and is not included here.
Ampacity
The current a conductor can carry safely. It is a separate check from voltage drop.

Assumptions and limits

Resistance only. It ignores reactance, which matters for large cables and AC, as well as bundling, harmonics and motor starting current. This tool does not check ampacity or protection. Wiring must follow your electrical code and be designed and installed by a qualified person. See the disclaimer.

Learn more