Three-phase power calculator

Find kW, kVA and kVAr for a balanced three-phase load.

A number above 0 and up to 1.

Apparent power
13.8564 kVA
Real power
12.4708 kW
Reactive power
6.03987 kVAr

Formula

S = √3 × V × I, P = S × PF, Q = √(S² − P²)

V is the line-to-line voltage, I is the line current and PF is the power factor. The same formulas apply to star and delta connections when line values are used.

Diagram

Three-phase powerL1L2L3120°S = √3 × V × I P = S × power factorV = line-to-line voltage, I = line current
The three line currents are 120° apart in time. For a balanced load, apparent power is √3 × V × I whatever the phase angle.

How it is calculated

  1. Enter the line-to-line voltage, the line current and the power factor.
  2. Apparent power: S = √3 × V × I, in volt-amperes.
  3. Real power: P = S × power factor, in watts.
  4. Reactive power: Q = √(S² − P²). Divide by 1,000 for kVA, kW and kVAr.

The √3 factor comes from the 120° phase difference between the three phases.

Worked examples

  1. A 400 V load

    400 V, 20 A and power factor 0.9. Result: Apparent power: 13.8564 kVA; Real power: 12.4708 kW; Reactive power: 6.03987 kVAr.

  2. A 415 V motor

    415 V, 32 A and power factor 0.8. Result: Apparent power: 23.0016 kVA; Real power: 18.4013 kW; Reactive power: 13.801 kVAr.

  3. A large 480 V load

    480 V, 100 A and power factor 0.95. Result: Apparent power: 83.1384 kVA; Real power: 78.9815 kW; Reactive power: 25.96 kVAr.

Key terms

Line-to-line voltage
The voltage measured between any two of the three phase conductors.
Line current
The current flowing in each phase conductor.
Apparent power (kVA)
The total power the supply must deliver, combining useful and reactive parts.
Real power (kW)
The power that does useful work, such as turning a shaft or producing heat.
Reactive power (kVAr)
Power that swings back and forth in inductive or capacitive loads and does no net work.
Power factor
Real power divided by apparent power. Motors typically run below 1.
Balanced load
A load drawing equal current in all three phases.

Assumptions and limits

Balanced three-phase loads only. Unbalanced loads, harmonics and starting currents need more detailed analysis. Electrical work must follow local code and be done by a qualified person. See the disclaimer.